10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.
These 10 free WA-JE questions are organized by exam domain, so you can see how each part of the Washington Journey Level (General 01) Electrician Certification Exam blueprint is tested. Reveal the answer and explanation under each question.
Domain 1: NEC 90 - Introduction
Question 1
During a design review, an engineer flags an ordinary branch circuit with 3.8% voltage drop and cites the NEC informational note recommending 3%. The load will receive voltage within its specified operating range. No special-occupancy voltage-drop requirement, local amendment, or tighter project specification applies. How should the electrician characterize the note's effect?
Show answer & explanation
Correct answer: C - It provides design guidance but does not, by itself, establish an enforceable violation.
Domain 3: NEC 200-225, 280-285 - Wiring & Protection
Question 2
Two 20 A single-pole breakers on opposite legs supply a 120/240 V multiwire branch circuit. Every load is connected line to neutral; no load uses both ungrounded conductors. The breakers have no handle tie. All other branch-circuit requirements are satisfied. What is the least change that provides the required simultaneous disconnection under the 2020 NEC?
Show answer & explanation
Correct answer: D - Add an identified handle tie suitable for the two installed breakers.
Domain 4: NEC 230 - Services
Question 3
Review four service designs under 2020 NEC 230.95. Each has a single service disconnect and supplies ordinary commercial loads; no exception to that section applies. Which design requires service ground-fault protection of equipment?
Show answer & explanation
Correct answer: D - 480Y/277 V, solidly grounded wye; 1,200 A disconnect.
Domain 6: NEC 250 - Grounding & Bonding
Question 4
A newly installed four-wire feeder supplies a detached workshop. At the workshop panel, the neutral bar is bonded to the enclosure; the feeder equipment grounding conductor (EGC) and local grounding electrode conductor are connected to the enclosure's grounding bar. A clamp meter detects current on the feeder EGC that rises as 120 V workshop loads are switched on. With the system safely deenergized for repair, which change removes the unintended neutral-current path while preserving required grounding?
Show answer & explanation
Correct answer: B - Isolate the neutral bar from the enclosure; retain the feeder EGC and the local grounding electrode connections.
Domain 7: NEC 300-398 - Wiring Methods
Question 5
A 70 ft raceway contains three 240 V, two-wire circuits and one wire-type equipment grounding conductor. The six circuit conductors are 6 AWG copper THHN/THWN-2, and all terminals are rated 75°C. Ambient temperature is 38°C. Table ampacities are 65 A at 75°C and 75 A at 90°C. The ambient correction factor for 90°C insulation is 0.91; conductor-count adjustment factors are 80% for 4-6 current-carrying conductors and 70% for 7-9. What is the greatest allowable conductor ampacity under these conditions?
Show answer & explanation
Correct answer: B - 54.6 A
Question 6
A junction box will contain six 12/2-with-ground cables, one duplex receptacle on a single yoke, and internal cable clamps. Every insulated conductor enters and is spliced or terminated in the box; all six equipment grounding conductors also enter. All conductors are 12 AWG, and any pigtails stay entirely inside. The volume allowance for 12 AWG is 2.25 in³. Using the 2020 NEC box-fill rules, select the smallest listed box volume that accommodates this assembly.
Show answer & explanation
Correct answer: C - 38.0 in³
Domain 9: NEC 430-450 - Motors, HVAC, Generators & Transformers
Question 7
An air-conditioning unit is marked 'Minimum Circuit Ampacity 28 A' and 'Maximum Fuse or Circuit Breaker 45 A.' Its proposed supply uses 10 AWG copper THHN/THWN-2 on 75°C terminals and a 40 A circuit breaker. The usable conductor ampacity is 35 A, no correction or adjustment is needed, and the breaker carries normal starting current. Under the 2020 NEC, how should this combination be judged?
Show answer & explanation
Correct answer: A - Accept it; 35 A satisfies MCA and 40 A is below the marked overcurrent maximum.
Domain 11: NEC 500-516 - Hazardous Locations
Question 8
Equipment is being selected for a location documented as Class I, Division 2, Group D. The vapor's autoignition temperature is 190°C. All candidates suit the site's ambient temperature. Which nameplate matches both the location classification and the temperature limitation?
Show answer & explanation
Correct answer: A - Class I, Division 2, Group D; T3A, maximum surface temperature 180°C.
Domain 17: Washington Laws & Rules (RCW & WAC)
Question 9
Recorded readings on a 120/240 V multiwire branch circuit show 120 V from each ungrounded conductor to neutral at the panel. At the connected loads, the readings are 158 V on one leg and 82 V on the other; line-to-line voltage remains 240 V. The two load voltages shift in opposite directions as appliances cycle. Which fault best explains this pattern?
Show answer & explanation
Correct answer: C - An open or high-resistance shared neutral between the panel and the connected loads.
Domain 18: General Trade Knowledge & Theory
Question 10
Today's crew for new 480Y/277 V factory distribution consists of one certified Washington general journey level (01) electrician, two registered apprentices holding valid electrical training certificates, and the contractor's electrical administrator. The administrator has no electrician certificate, and no school-program ratio exception applies. What staffing change is needed for both apprentices to perform this general electrical work at the same time?
Show answer & explanation
Correct answer: D - Add a second certified journey level or master journey level electrician to meet the one-to-one supervision ratio.